FSC system anomalies
I found mismatch during the test FSC logic. I
prepared several FLD pages for test. All FLDs work in FSC like in my program. But
results following FLD test were a big unexpectedness for me (See drawing and time
diagrams. All diagrams is based on FSC SOE records)
Most people can say - backward line is the reason of
this mistake. But following FLD work properly (see drawing and time
diagrams). Flip-flop was shift to right.
The reason is wrong sequence of execution. The
program code for flip-flop had executed before second "AND" gate. Anybody know
why it happens?
I think this is not a single incident! It is dangerous. FSC programmers must change algorithm or create special
tools for test existing logic.
You can download here wrong code block for test. I had executed tests on FSC
system release 5xx.
If you know any mistake in FSC system please send me description to the following address
mailto:dws_support@mail.ru |